India Trade Promotion Organisation, New Delhi invites
technical and commercial bids from authorized/experienced companies
for annual maintenance contract for 1 No. 15 KVA UPS installed in
Business Information Centre, Hall No.19, Pragati Maidan, New Delhi
for a period of three years.
Technical Specifications
Make of UPS
|
CONSUL - MEGALINE
|
Physical dimensions of the UPS and weight of the
UPS
|
(H*W*D in mm) = (1150*820*630) approx. Weight
= 275 Kgs.(UPS only)
|
| Make and AH of batteries |
Exide Power/AH is 12V* 28AH *30 Nos.
for computer load
|
Physical dimension of battery rack
|
(H*W*D in mm) = (650*350*400) approx.
|
| Capacity |
15 KVA UPS (Three Phase input and
three phase output)
|
| AC Input (3 phase, 4 Wire) |
415 V + 15% to 20% @ 50Hz +/-3 Hz
|
| AC output (single phase) |
|
| Rating |
Continuous
|
| Voltage |
415 V +/-1%
|
| Frequency |
50 Hz+ 0.1 Hz |
| Wave from |
Pure sine wave |
| Inverter Technology |
High frequency (25KHz) PWM using microprocessor
controlled IGBTs |
| Transient Response & Recovery |
For 100% step load, change in output
volt not exceeding 8% and recovery within 3 cycles |
| Inverter Efficiency |
91% - 94% at full load |
| THD |
3% on linear & complex load |
| Load Power Factor |
0.8 |
| Over load |
120% for 10 mins. (can be software
programmed for longer duration, however is strictly temperature
controlled)
150% for 5 Mins.
200% for 0.3 Secs. |
| Crest Factor |
3 : 1 |
| Metering |
The software provided alongwith CONSUL-MEGALINE
UPS can monitor the following parameters such as Output Voltage,
Current, Temperature, Power level etc. Upto 16 parameters can
be monitored. The software is extremely user friendly and very
easy to operate.
|
| Indications |
LED display for Mains On, Inverter
Over Load, Inverter On, Mains Fail Alarm, By-Pass Alarm, Battery
Low Alarm, Self Test, RMS Load Alarm, Peak Load Temperature,
Load on By-Pass.
|
| Protections |
3 Phase input MCB, over load inverter
trip, under voltage inverter trip, over voltage inverter trip,
battery charging current limit, short circuit inverter trip
|
| Soft Start |
Both available on charger and inverter
|
| Alarm |
Buzzer for battery low |
| Isolation |
Galvanic Isolation provided |
1. The firm/company should be in existence for over 5 years in the
trade with the maintenance business having service business turn
over of more than Rs.20 lakhs per annum during the last 2 years
ending March 31, 2007.
2. The firm/company should have a previous maintenance contract
for at least two years with a Government Department/Public Sector
Undertaking in Delhi. The company should furnish statement of previous
work for the last two years.
3. The firm/company must have expertise in on-site maintenance and
repair of UPS.
4. The firm/company should be authorized service provider/a business
partner of leading UPS manufacturers. Please attach a copy of valid
service authorization certificate from the manufacturer.
5. The firm/company should produce copies of documents relating
to allocation of service tax registration number VAT registration
number and PAN number.
6. The firm/company should submit a draft of Rs.4,500/- towards
earnest money deposit
Financial
1. The rate may be quoted on annual basis for UPS in a separate
sealed cover.
2. The other terms & conditions for awarding the AMC shall
be as follows:
· The AMC will be applicable for a period of 3 years from
the date of signing of the contract.
· The comprehensive maintenance includes preventive maintenance,
quarterly regular services of the UPS, etc. and/or replacement
of any items necessary for keeping the 15 KVA UPS active and free
from any defects or disturbance and also on any unscheduled call
for corrective and maintenance services, taking appropriate measures/steps
on time to set right the malfunctioning of the UPS. The replacement
of all the spares including batteries, etc. is included under
the maintenance contract. The replacement of defective spares
with original spares or spares of equivalent specification will
be done by the AMC company, without any extra charge of any kind.
· The AMC charges will be payable at the end of each year
based on satisfactory services for the quarter.
· All taxes VAT, octroi, service tax, etc.
if any, should be included in the prices quoted for the AMC.
· Quotes should cover quarterly preventive maintenance and
when called for in the event of break-down.
· Please quote service tax registration no., VAT registration
no. and PAN no. in your offer.
· The jurisdiction in case of disputes shall be the courts
of Delhi/New Delhi.
· ITPO can accept or reject any offer at its discretion
without assigning any reason, whatsoever.
The tender documents can be collected in person on payment of Rs.500/-
(non refundable) in cash or by way of demand draft of the said amount
favouring India Trade Promotion Organisation payable at New Delhi.
Tender form can be downloaded from our website:
www.indiatradefair.com
and the tender cost deposited alongwith the bid by way of demand
draft. The last date for sale of tender document is 11.4.2007.
Technical and commercial bids are required to be submitted
separately
in sealed covers marked "QUOTATIONS FOR AMC FOR 15 KVA UPS
FOR BIC" written on the envelope and sent to Mrs. S. Swami,
Sr. Manager, Computer Department, India Trade Promotion Orgnaisation,
Ground Floor, Pragati Bhawan (Annexe II), Pragati Maidan, New Delhi-110
001, latest by 18.4.2007 upto 3.00PM.. The Technical bids will be
opened on the same date at 3.30PM. The intimation for opening of
Financial Bids of only successful Technical Bidder will be communicated
separately.